AAI543-H53 Yokogawa Analog Modules AAI 543-H53

AAI543-H53 Yokogawa Analog Modules AAI 543-H53

Model Number:

Product Type:DCS IO Card

Type:a:1:{i:0;s:19:”Packaging machinery”;}

Category:Yokogawa AAI Series

Plance of Origin:Made in Japan

Warranty:All the Parts one year warranty

Description:Yokogawa Analog Modules  

Part Number:AAI543-H53

Yokogawa Analog Output Module:Analog Input Module, 4 to 20 mA, 16-channel, Isolated, HART protocol

Current Output Module (Isolated)

AAI543 provides 16 outputs of 4 – 20 mA signal. It can be used in dual-redundant configuration. (*1)

 

Items Specifications
Model AAI543
Number of output channels 16, isolated, standard switch-over
response in redundant configuration (*3)
Output signal 4 to 20 mA
Withstanding voltage Between output and system: 1500 V AC, for 1 minute (4)
Allowable load resistance 0 to 750 Ω
Circuit-open detection Less than 0.65 mA
Accuracy ±48 μA
Data update period 10 ms
Drift due to ambient temperature change ±16 μA/10 C
Maximum current consumption 230 mA (5 V DC), 540 mA (24 V DC)
Weight 0.4 kg
External communication Pressure clamp terminal, MIL connector cable, dedicated cable (KS1)
HART communication (5) Available

*1: A dual-redundant configuration is enabled by using two identical modules with the same suffix codes.
*2: When AAI543 is installed in a ER bus node unit, use it in the ambient temperature within 0 to 60 ºC range.
*3: When a switch over from control to stand-by module takes place in the dual-redundant configuration, the maximum period
of time when the field output falls below 4 mA is 100 ms for AAI543-0 (standard switch-over response) and 2 ms for
AAI543-1(fast switch-over response). In case of connecting fast response type field devices, use AAI543-1 (fast
switch-over response) in the dual-redundant configuration.
*4: When the dedicated cable is used, the withstanding voltage is 500 V AC (between the input signal and the system). When
the ML connector cable is used, the withstanding voltage depends on the electrical specifications of the cable.
*5: When this module is installed in a ER bus node unit with HART function, the EB401 firmware must be rev. 2 or later.

Yokogawa Analog Output Module AAI543-H53

MODEL AND SUFFIX CODES AAI543-H53

Description
Model AAI543 Analog Output Module (4 to 20 mA 16-channel Isolated)
-S Standard Type
-H With digital communication (HART protocol)
Suffix
Codes
5 Standard switch-over response in redundant configuration with no explosion protection(*1)
6 Fast switch-over response in redundant configuration with no explosion protection(*2)
E Standard switch-over response in redundant configuration with explosion protection(*1)
F Fast switch-over response in redundant configuration with explosion protection(*2)
0 Basic type
1 With ISA Standard G3 option
3 With ISA Standard G3 option and temperature (-20 to 70 C) option
Option
Codes
/K4A00 With KS Cable Interface Adapter [Model ATK4A-00]
/A4S00 With Pressure Clamp Terminal Block for Analog [Model ATA4S-00]
/A4S10 With Pressure Clamp Terminal Block for Analog (surge absorber) [Model ATA4S-10]
/A4D00 With Dual Pressure Clamp Terminal Block for Analog [Model ATA4D-00]
/A4D10 With Dual Pressure Clamp Terminal Block for Analog (surge absorber) [Model ATA4D-10]
/CCC01 With Connector Cover for MIL Cable [Model ACCC01]

 

*1: If “standard switch-over response in redundant configuration” is selected, “basic type” or “with ISA Standard G3 option and
temperature (-20 to 70 °C) option” may be specified.
*2: If “fast switch-over response in redundant configuration” is selected, “basic type” or “with ISA Standard G3 option” may be
specified.